3.3.1 Summary of Required Simulations
Separate rating analyses are required for each purpose. Runs 1 through 20 are required when software is accredited for green building ratings that use ASHRAE Standard 90.1-2007 as the baseline. Runs 21 through 29 are required for tax credits that use ASHRAE Standard 90.1-2001 as the baseline. See Table 3.3.1-1. Runs 30 through 49 are required when software is accredited for green building ratings that use ASHRAE Standard 90.1-2010 as the baseline.
| Run | Purpose | Prototype | Climate | Occupancy Option | Lighting Power Density (W/ft²) | Equipment Power Density (W/ft²) | HVAC System | Default Schedules |
| 1 | Points07 | A1 | Chicago | Office | 1.00 | 1.00 | PSZ-AC | Yes |
| 2 | Points07 | A1 | Chicago | Office | 1.20 | 1.50 | PSZ-HP | No |
| 3 | Points07 | A1 | Chicago | Office | 1.40 | 2.00 | PVAV | No |
| 4 | Points07 | A1 | Denver | Office | 1.00 | 1.00 | PSZ-AC | Yes |
| 5 | Points07 | A1 | Miami | Office | 1.00 | 1.00 | PSZ-AC | Yes |
| 6 | Points07 | A3 | Chicago | Office | 1.00 | 1.00 | PVAV | Yes |
| 7 | Points07 | A3 | Denver | Office | 1.00 | 1.00 | PVAV | Yes |
| 8 | Points07 | A3 | Miami | Office | 1.00 | 1.00 | PVAV | Yes |
| 9 | Points07 | A20 | Chicago | Office | 1.00 | 1.00 | VAV | Yes |
| 10 | Points07 | A20 | Denver | Office | 1.00 | 1.00 | VAV | Yes |
| 11 | Points07 | A20 | Miami | Office | 1.00 | 1.00 | VAV | Yes |
| 12 | Points07 | B1 | Chicago | Supermarket | 2.10 | 0.20 | PSZ-AC | Yes |
| 13 | Points07 | B1 | Denver | Retail | 1.90 | 0.90 | PSZ-AC | Yes |
| 14 | Points07 | B1 | Miami | Manufacturing | 1.30 | 1.00 | PSZ-HP | Yes |
| 15 | Points07 | C1 | Chicago | Retail | 1.50 | 0.90 | PSZ-AC | Yes |
| 16 | Points07 | C1 | Denver | Warehouse | 0.80 | 0.40 | PSZ-AC | Yes |
| 17 | Points07 | C1 | Miami | Manufacturing | 1.30 | 1.00 | PSZ-HP | Yes |
| 18 | Points07 | D | Chicago | See detail | See detail | See detail | See detail | Yes |
| 19 | Points07 | D | Denver | See detail | See detail | See detail | See detail | Yes |
| 20 | Points07 | D | Miami | See detail | See detail | See detail | See detail | Yes |
| 21 | Tax | A1 | Chicago | Office | 1.00 | 1.00 | PSZ-AC | Yes |
| 22 | Tax | A1 | Denver | Office | 1.00 | 1.00 | PSZ-AC | Yes |
| 23 | Tax | A1 | Miami | Office | 1.00 | 1.00 | PSZ-AC | Yes |
| 24 | Tax | B1 | Chicago | Supermarket | 2.10 | 0.20 | PSZ-AC | Yes |
| 25 | Tax | B1 | Denver | Retail | 1.90 | 0.90 | PSZ-AC | Yes |
| 26 | Tax | B1 | Miami | Manufacturing | 1.30 | 1.00 | PSZ-HP | Yes |
| 27 | Tax | D | Chicago | See detail | See detail | See detail | See detail | Yes |
| 28 | Tax | D | Denver | See detail | See detail | See detail | See detail | Yes |
| 29 | Tax | D | Miami | See detail | See detail | See detail | See detail | Yes |
| 30 | Points10 | A1 | Chicago | Office | 1.00 | 1.00 | PSZ-AC | Yes |
| 31 | Points10 |
A1 | Chicago | Office | 1.20 | 1.50 | PSZ-HP | No |
| 32 | Points10 | A1 | Chicago | Office |
1.40 | 2.00 | PVAV | No |
| 33 | Points10 | A1 | Denver | Office | 1.00 | 1.00 | PSZ-AC | Yes |
| 34 | Points10 | A1 | Miami | Office | 1.00 | 1.00 | PSZ-AC | Yes |
| 35 | Points10 | A3 | Chicago | Office | 1.00 | 1.00 | PVAV | Yes |
| 36 | Points10 | A3 | Denver | Office | 1.00 |
1.00 | PVAV | Yes |
| 37 | Points10 | A3 | Miami | Office | 1.00 | 1.00 | PVAV | Yes |
| 38 | Points10 | A20 | Chicago | Office | 1.00 | 1.00 | VAV | Yes |
| 39 | Points10 | A20 | Denver | Office | 1.00 | 1.00 | VAV | Yes |
| 40 | Points10 | A20 | Miami | Office | 1.00 | 1.00 | VAV | Yes |
| 41 | Points10 | B1 | Chicago | Supermarket | 2.10 | 0.20 | PSZ-AC | Yes |
| 42 | Points10 | B1 | Denver | Retail | 1.90 | 0.90 | PSZ-AC | Yes |
| 43 | Points10 | B1 | Miami | Manufacturing | 1.30 | 1.00 | PSZ-HP | Yes |
| 44 | Points10 | C1 | Chicago | Retail | 1.50 | 0.90 | PSZ-AC | Yes |
| 45 | Points10 | C1 | Denver | Warehouse | 0.80 | 0.40 | PSZ-AC | Yes |
| 46 | Points10 | C1 | Miami | Manufacturing | 1.30 | 1.00 | PSZ-HP | Yes |
| 47 | Points10 | D | Chicago | See detail | See detail | See detail | See detail | Yes |
| 48 | Points10 | D | Denver | See detail | See detail | See detail | See detail | Yes |
| 49 | Points10 | D | Miami | See detail | See detail | See detail | See detail | Yes |
- PDF Version of Visible Section/s
- Generate Complete PDF
- Printer-friendly Version
- Login or register to post comments
Select a Purpose
Download PDF
Book Navigation
- Commercial Buildings Energy Modeling Guidelines & Procedures (MGP)
- Acknowledgments
- 1 Overview
- 2 General Modeling Procedures
- 3 Software Requirements
- 4 Content and Format of Standard Reports
- 5 Energy Costs and Currency Specification
- 6 Building Decriptors Reference
- 6.1 Overview
- 6.2 Project Data
- 6.3 Thermal Blocks
- 6.4 Space Uses
- 6.5 Building Envelope Data
- 6.6 HVAC Zone Level Systems
- 6.7 HVAC Secondary Systems
- 6.8 HVAC Primary Systems
- 6.9 Miscellaneous Energy Uses
- 6.10 On-Site Power Generation
- 6.11 Common Data Structures
- 6.11.1 Schedule
- 6.11.2 Holidays
- 6.11.3 Surface Geometry
- 6.11.4 Opening Geometry
- 6.11.5 Opening Shade
- 6.11.6 Construction Assembly
- 6.11.7 Fenestration Construction
- 6.11.8 Material
- 6.11.9 Slab Construction
- 6.11.10 Exterior Surface Properties
- 6.11.11 Building Shade
- 6.11.12 Utility Rate
- 6.11.13 Occupant Heat Rate
- 6.11.14 Furniture and Contents
- 6.11.15 Reference Position in a Space
- 6.11.16 Two Dimensional Curve
- 6.11.17 Three Dimensional Curve
- 6.11.18 Temperature Reset Schedule
- 6.11.19 Photovoltaic (PV) Panel
- 6.11.20 Contact
- 7 Advanced Modeling Tips
- 7.1 Challenging Building Types
- 7.2 Design Features
- 7.2.1 Automatically Controlled Window Shades
- 7.2.2 Active Chilled Beams
- 7.2.3 Dedicated Outside Air Systems (DOAS)
- 7.2.4 Displacement ventilation
- 7.2.5 Gas Engine Driven Heat Pumps
- 7.2.6 Ground Source Heat Pumps
- 7.2.7 Ice Storage Air Conditioners
- 7.2.8 Radiant Heating and/or Cooling
- 7.2.9 Switchable glazing
- 7.2.10 UFAD
- 7.2.11 Variable Refrigerant Flow
- Download Appendices