6.4.3 Interior Lighting
The building descriptors in this section are provided for each lighting system. Typically a space will have only one lighting system, but in some cases, it could have two or more. Examples include a general and task lighting system in offices or hotel multi-purpose rooms that have lighting systems for different functions.
| Regulated Interior Lighting Power |
|
| Applicability | All projects |
|---|---|
| Definition | Total connected lighting power for all regulated interior lighting power. This includes the loads for lamps and ballasts. |
| Units | W/ft² |
| Input Restrictions | As designed. The connected power should be cross-referenced to a space type and to the construction documents |
| Baseline Rules |
With the building classification method, use the product of the lighting power density for the building classification from Appendix B and the floor area of the space. With the space-by-space method, use the product of the lighting power densities for the space-by-space from Appendix B and the floor areas for the corresponding spaces. |
| Non-Regulated Interior Lighting Power |
|
| Applicability | All projects |
|---|---|
| Definition |
Power for the following lighting equipment and applications are exempt from the baseline standards, provided they are controlled by an independent control device:
In addition, lighting is exempt that is specifically designated as required by a health or life safety statute, ordinance, or regulation for reasons of safety or security. Emergency lighting that is automatically off during normal building operation is not considered. |
| Units | W/ft² |
| Input Restrictions | As designed. The non-regulated lighting power should be cross-referenced to the type of exception and to the construction documents. The default for non-regulated lighting power is zero. |
| Baseline Rules | The non-regulated interior lighting in the baseline building shall be the same as the proposed design. |
| Lighting Schedules |
|
| Applicability | All projects |
|---|---|
| Definition | Schedule of operation for interior lighting power used to adjust the energy use of lighting systems on an hourly basis to reflect time-dependent patterns of lighting usage. Different schedules may be defined for different lighting circuits, depending on the capabilities of the software. |
| Units | Data structure: schedule, fractional |
| Input Restrictions | The lighting schedule is prescribed for tax deductions. The lighting schedule is a default for green building ratings and Design to Earn ENERGY STAR. For tax deductions, an appropriate schedule from Appendix C Tables 12-16 for the California 2005 ACM shall be used. For green building ratings and Design to Earn ENERGY STAR, the default schedules are presented in Appendix C. |
| Baseline Rules | The baseline building shall use the same lighting schedules as the proposed design. The only exception to this rule is when the proposed design has a task/ambient lighting system. In this case the proposed design task lighting system may be controlled on a different schedule and the proposed design schedule proposed for the ambient lighting system is used for all the lighting in the baseline building. |
| Retail Display Lighting Power |
||
| Applicability | Display lighting in retail display and other space-by-space classifications | |
|---|---|---|
| Definition |
Display lighting is special lighting to highlight merchandise. Its purpose is to enhance the visual appearance of the merchandise and not to provide lighting for a visual task. Display lighting is treated as use-it-or-lose-it in ASHRAE Standard 90.1. To qualify for display lighting, the lighting must be separately controlled from the general lighting.
ASHRAE Standard 90.1-2007 defines four categories of display lighting:
|
|
| Units | W or W/ft² | |
| Input Restrictions | As designed. The default for lighting power for retail display wattage is 0.0 watts. When display lighting is entered in the software, its purpose shall be defined (see the categories above in the definitions section). | |
| Baseline Rules | Baseline building lighting power is the lesser of proposed design power or the allowed power. The allowed lighting power is defined as the floor area of the retail display times the allowances in Table 6.4.3-1. | |
| ASHRAE Standard 90.1-2007 | ||
| Category | Allowed Power (W/ft²) | |
| Retail Area 1 | 1.0 | |
| Retail Area 2 |
1.7 | |
| Retail Area 3 |
2.6 | |
| Retail Area 4 |
4.2 |
| Decorative Lighting Power |
|
| Applicability | All projects that have decorative lighting and are rated using the space-by-space method |
|---|---|
| Definition |
Decorative lighting includes wall sconces, chandeliers and other decorative lighting that is provided for purposes other than illuminating visual tasks. The baseline standards treat this lighting as use-it-or-lose-it. |
| Units | W or W/ft2 |
| Input Restrictions | As designed. The default for decorative lighting power is 0.0 watts/ft2. When using the space-by-space method, the user may input the power for qualifying decorative lighting using the decorative lighting power descriptor and cross-referencing the construction documents. |
| Baseline Rules | For the space-by-space method, decorative lighting power in the baseline building is equal to the lesser of the actual wattage of decorative lighting specified for the proposed design or 1.0 W/ft2. |
| Lighting Power for VDT Viewing |
|
| Applicability | Tax deductions only (ASHRAE Standard 90.1-2001 baseline) |
|---|---|
| Definition |
ASHRAE Standard 90.1-2001 provided additional lighting in spaces that are intended for use with video display terminals (VDT). This special allowance was eliminated with ASHRAE Standard 90.1-2007 and only applies for the purpose of calculating tax deductions. In order for a space to qualify for the special allowance, the specified luminaires must have special optical characteristics that direct most of the light down and minimize light cast to the sides. Specifically, a qualifying luminaire must serve a VDT viewing task and provide a maximum luminance measured from the vertical of 80 candelas/ft2 at 65 degrees, 33 candelas/ft2 75 degrees and 17 candelas/ft2 at 85 degrees or greater. |
| Units | W/ft2 |
| Input Restrictions | As designed. The default for lighting power for VDT viewing is 0.0 watts/ft2 . The user may input qualifying lighting power for qualifying areas with cross-references to lighting schedules and spaces on the construction documents. A cut-sheet tabulating the candela distribution of the luminaires shall be provided. |
| Baseline Rules | The allowed lighting power for qualifying spaces is increased by 0.35 W/ft2 from the allowed values in Appendix B. |
|
Light Heat Gain Distribution |
|
| Applicability | All projects |
|---|---|
| Definition |
The distribution of the heat generated by the lighting system that is directed to the space, the plenum, the HVAC return air, or to other locations. This input is a function of the luminaire type and location. Luminaires recessed into a return air plenum contribute more of their heat to the plenum or the return air stream if the plenum is used for return air; while pendant mounted fixtures hanging in the space contribute more of their heat to the space. Common luminaire type/space configurations are listed in Table 3, Chapter 18, 2009 ASHRAE Handbook – Fundamentals, summarized in Table 6.4.3-1 below. Typically the data will be linked to list of common luminaire configurations similar to Table 6.4.3-1 so that the user chooses a luminaire type category and heat gain is automatically distributed to the appropriate locations. This input may also be used to approximate the benefit of displacement ventilation (see Chapter 7). |
| Units | List (of luminaire types) or data structure consisting of a series of decimal fractions that assign heat gain to various locations. |
| Input Restrictions | Default values listed in Table 6.4.3-1 shall be used as a default when the luminaire categories apply. Values within the ranges of Table 6.4.3-1 may be used when following the rules in the 2009 HOF. Other values may be used when manufacturers’ literature and/or testing data is available, and adequate documentation is provided to the rating authority. Where lighting fixtures having different heat venting characteristics are used within a single space, the wattage weighted average heat-to-return-air fraction shall be used. |
| Baseline Rules | The baseline building shall use the above referenced defaults. |
Source: 3, Table 3, Chapter 18, 2009 ASHRAE Handbook – Fundamentals
| Luminaire Category | Space Fraction | Radiative Fraction |
| Recessed fluorescent luminaire without lens | 0.64 to 0.74 (default 0.69) | 0.48 to 0.68 (default 0.58) |
| Recessed fluorescent luminaire with lens | 0.40 to 0.50 (default 0.45) | 0.61 to 0.73 (default 0.67) |
| Downlight compact fluorescent luminaire | 0.12 to 0.24 (default 0.18) | 0.95 to 1.00 (default 0.97) |
| Downlight incandescent luminaire | 0.70 to 0.80 (default 0.75) | 0.95 to 1.00 (default 0.97) |
| Non-in-ceiling fluorescent luminaire | 1.0 (default 1.0) | 0.50 to 0.57 (default 0.53) |
| Power Adjustment Factors (PAF) |
|
| Applicability | All projects |
|---|---|
| Definition | Automatic controls that are not already required by the baseline standard and which reduce lighting power more or less uniformly over the day can be modeled as power adjustment factors. Power adjustment factors represent the percent reduction in lighting power that will approximate the effect of the control. Models account for such controls by adjusting the installed power by (1 – PAF). The types of controls that are recognized for credit are listed in ASHRAE Standard 90.1-2007, Appendix G, Table G3.2 and shown below in Table 6.4.3-3. |
| Units | List: control types (see above) linked to PAFs |
| Input Restrictions | As designed |
| Baseline Rules | PAF is zero |
| Automatic Control Device | Non-24-hour occupied buildings that are less than 5,000 ft² | Other buildings |
| Programmable timing control | 10% | 0% |
| Occupant sensor | 15% | 10% |
| Occupant sensor and programmable timing controls | 15% | 10% |
| Bi-level parking garage controls1 | 30% | 30% |
| Bi-level controls in hotel corridors | 20% | 20% |
| Scene controller with timeclock | 20% | 20% |
- 1. Bi-level Smart LED Parking Garage Lighting, Public Interest Energy Research Program IOU Partnership Draft-Case Study
http://cltc.ucdavis.edu/images/_projects/demonstration/bi_level_smart_led_parking_garage_lighting/pier_demo_uc_csu_bi_level_smart_led_parking_garage_lighting.pdf
- PDF Version of Visible Section/s
- Generate Complete PDF
- Printer-friendly Version
- Login or register to post comments
Select a Purpose
Download PDF
Book Navigation
- Commercial Buildings Energy Modeling Guidelines & Procedures (MGP)
- Acknowledgments
- 1 Overview
- 2 General Modeling Procedures
- 3 Software Requirements
- 4 Content and Format of Standard Reports
- 5 Energy Costs and Currency Specification
- 6 Building Decriptors Reference
- 6.1 Overview
- 6.2 Project Data
- 6.3 Thermal Blocks
- 6.4 Space Uses
- 6.5 Building Envelope Data
- 6.6 HVAC Zone Level Systems
- 6.7 HVAC Secondary Systems
- 6.8 HVAC Primary Systems
- 6.9 Miscellaneous Energy Uses
- 6.10 On-Site Power Generation
- 6.11 Common Data Structures
- 6.11.1 Schedule
- 6.11.2 Holidays
- 6.11.3 Surface Geometry
- 6.11.4 Opening Geometry
- 6.11.5 Opening Shade
- 6.11.6 Construction Assembly
- 6.11.7 Fenestration Construction
- 6.11.8 Material
- 6.11.9 Slab Construction
- 6.11.10 Exterior Surface Properties
- 6.11.11 Building Shade
- 6.11.12 Utility Rate
- 6.11.13 Occupant Heat Rate
- 6.11.14 Furniture and Contents
- 6.11.15 Reference Position in a Space
- 6.11.16 Two Dimensional Curve
- 6.11.17 Three Dimensional Curve
- 6.11.18 Temperature Reset Schedule
- 6.11.19 Photovoltaic (PV) Panel
- 6.11.20 Contact
- 7 Advanced Modeling Tips
- 7.1 Challenging Building Types
- 7.2 Design Features
- 7.2.1 Automatically Controlled Window Shades
- 7.2.2 Active Chilled Beams
- 7.2.3 Dedicated Outside Air Systems (DOAS)
- 7.2.4 Displacement ventilation
- 7.2.5 Gas Engine Driven Heat Pumps
- 7.2.6 Ground Source Heat Pumps
- 7.2.7 Ice Storage Air Conditioners
- 7.2.8 Radiant Heating and/or Cooling
- 7.2.9 Switchable glazing
- 7.2.10 UFAD
- 7.2.11 Variable Refrigerant Flow
- Download Appendices
