6.5.3 Roofs
| Roof Name |
|
| Applicability | All roof surfaces |
|---|---|
| Definition | A unique name or code that identifies the roof and ties it to the construction documents submitted for energy code review. It is not mandatory to name roofs. |
| Units | Text, unique |
| Input Restrictions | None |
| Baseline Rules | None |
| Roof Type |
|
| Applicability | All roof surfaces |
|---|---|
| Definition | One of three classifications of roofs defined in the baseline standard. These classifications are defined in ASHRAE Standard 90.1-2001 and ASHRAE Standard 90.1-2007 along with the associated User's Manuals. The prescriptive U-factor requirements for roofs depend on the type. For green building ratings and tax credits, it is not necessary to specify this information, as the PRM fixes the type for the baseline building to “insulation entirely above the deck.” This descriptor can be derived from other building descriptors and it may not be necessary for the software user to specify it directly. |
| Units | List: attic and other roofs; metal building roofs; and roofs with insulation entirely above deck. |
| Input Restrictions | This input is optional for the purposes covered by this manual. |
| Baseline Rules | All roofs in the baseline building are modeled as “insulation entirely above deck.” |
| Roof Geometry |
|
| Applicability | All roofs, required input |
|---|---|
| Definition | Roof geometry defines the position, orientation, azimuth, tilt, and dimensions of the roof surface. The details of how the coordinate system is implemented may vary between software programs. The data structure for surfaces is described in the reference section of this chapter. |
| Units | Data structure: surface |
| Input Restrictions | There are no restrictions other than that the surfaces defined must agree with the building being modeled, as represented on the construction drawings or as-built drawings. |
| Baseline Rules | Roof geometry will be identical in the proposed and baseline building designs. |
| Roof Construction |
|
| Applicability | All roofs, required input |
|---|---|
| Definition | A reference to a construction assembly for the proposed design. See the building descriptors above for construction assemblies. |
| Units | Dimensionless reference |
| Input Restrictions | All roof surfaces must reference a construction assembly. |
| Baseline Rules | Roofs in the baseline building are of the type “insulation entirely above deck.” The insulation requirement is determined by climate zone and is given in Table 6.5.3-1. The baseline building roof construction shall be modeled as layers as defined in Table 6.5.3-2. These tables reflect a construction that is available in the standard list of constructions. |
| Applicable Standard | Space Category | Climate Zone | Standard Design | |
| Minimum Insulation | Maximum Assembly | |||
| 90.1 – 2001 |
Nonresidential | 1-7 | R-15 c.i. | U-0.063 |
| 8 | R-20 c.i. | U-0.048 | ||
| Residential | 1,2,3,4,5,6,7 | R-15 c.i. | U-0.063 | |
| 8 | R-20 c.i. | U-0.048 | ||
| Semi-Heated | 1 | NR | U-1.282 | |
| 2,3,4 | R-3.8 c.i. | U-0.218 | ||
| 5,6,7 | R-5.0 c.i. | U-0.173 | ||
| 8 | R-10.0 c.i. | U-0.093 | ||
| 90.1 – 2007 and 90.1 – 2010 | Nonresidential | 1 | R-15 c.i. | U-0.063 |
| 2-8 | R-20 c.i. | U-0.048 | ||
| Residential | 1-8 | R-20 c.i. | U-0.048 | |
| Semi-Heated | 1, 2 | R-3.8 c.i. | U-0.218 | |
| 3, 4 | R-5.0 c.i. | U-0.173 | ||
| 5 | R-7.6 c.i | U-0.119 | ||
| 6,7 | R-10.0 c.i. | U-0.093 | ||
| 8 | R-15.0 c.i. | U-0.063 | ||
| Construction | Layer | Thickness (inch) | Conductivity (Btu/h ft F) | Density (lb/ft²) | Specific Heat (Btu/lb F) | R-value (ft²·°F·h/Btu) | U-factor (Btu/h-ft²-F) |
| Roof R-20 c.i. | Exterior air film | 0.17 | |||||
| Roofing membrane | 0.00 | ||||||
| R-20 continuous insulation | 4.8 | 0.02 | 1.8 | 0.29 | 20.00 | ||
| Steel deck | 0.06 | 26 | 480 | 0.10 | 0.00 | ||
| Interior air film | 0.61 | ||||||
| Total for assembly | 20.78 | 0.048 | |||||
| Roof R-15 c.i. | Exterior air film | 0.17 | |||||
| Roofing membrane | 0.00 | ||||||
| R-15 continuous insulation | 3.6 | 0.02 | 1.8 | 0.29 | 15.00 | ||
| Steel deck | 0.06 | 26 | 480 | 0.10 | 0.00 | ||
| Interior air film | 0.61 | ||||||
| Total for assembly | 15.78 | 0.063 | |||||
| Roof R-10 c.i. | Exterior air film | 0.17 | |||||
| Roofing membrane | 0.00 | ||||||
| R-10 continuous insulation | 2.4 | 0.02 | 1.8 | 0.29 | 10.00 | ||
| Steel deck | 0.06 | 26 | 480 | 0.10 | 0.00 | ||
| Interior air film | 0.61 | ||||||
| Total for assembly | 10.78 | 0.093 | |||||
| Roof R-7.6 c.i. | Exterior air film | 0.17 | |||||
| Roofing membrane | 0.00 | ||||||
| R-7.6 continuous insulation | 1.8 | 0.02 | 1.8 | 0.29 | 7.6 | ||
| Steel deck | 0.06 | 26 | 480 | 0.10 | 0.00 | ||
| Interior air film | 0.61 | ||||||
| Total for assembly | 8.38 | 0.119 | |||||
| Roof R-5 c.i. | Exterior air film | 0.17 | |||||
| Roofing membrane | 0.00 | ||||||
| R-5 continuous insulation | 1.2 | 0.02 | 1.8 | 0.29 | 5.00 | ||
| Steel deck | 0.06 | 26 | 480 | 0.10 | 0.00 | ||
| Interior air film | 0.61 | ||||||
| Total for assembly | 5.78 | 0.173 | |||||
| Roof R-3.8 c.i. | Exterior air film | 0.17 | |||||
| Roofing membrane | 0.00 | ||||||
| R-3.8 continuous insulation | 0.9 | 0.02 | 1.8 | 0.29 | 3.80 | ||
| Steel deck | 0.06 | 26 | 480 | 0.10 | 0.00 | ||
| Interior air film | 0.61 | ||||||
| Total for assembly | 4.58 | 0.218 | |||||
| NR. | Exterior air film | 0.17 | |||||
| Roofing membrane | 0.00 | ||||||
| Steel deck | 0.06 | 26 | 480 | 0.10 | 0.00 | ||
| Interior air film | 0.61 | ||||||
| Total for assembly | 5.78 | 1.282 |
| Exterior Roof Surface Properties |
|
| Applicability | All roofs |
|---|---|
| Definition | The exterior roof surface properties descriptor defines the characteristics of exterior surfaces. Exterior surface properties include emissivity, reflectivity and roughness. The first two govern radiation exchange from the surface, while the latter governs the magnitude of the exterior air film resistance. |
| Units | Data structure: exterior surface properties |
| Input Restrictions | The default value is a reflectance of 0.30 and an emittance of 0.75. The default value may be overridden when roof materials are used that have been tested by the Cool Roof Rating Council (CRRC) and are called for in the construction documents. In cases where the default value is overridden, the user is required to submit documentation identifying the test procedure that was used to establish the non-default values. |
| Baseline Rules | The default values (see Input Restrictions above) shall be used for roofs for the baseline building. |
- PDF Version of Visible Section/s
- Generate Complete PDF
- Printer-friendly Version
- Login or register to post comments
Select a Purpose
Download PDF
Book Navigation
- Commercial Buildings Energy Modeling Guidelines & Procedures (MGP)
- Acknowledgments
- 1 Overview
- 2 General Modeling Procedures
- 3 Software Requirements
- 4 Content and Format of Standard Reports
- 5 Energy Costs and Currency Specification
- 6 Building Decriptors Reference
- 6.1 Overview
- 6.2 Project Data
- 6.3 Thermal Blocks
- 6.4 Space Uses
- 6.5 Building Envelope Data
- 6.6 HVAC Zone Level Systems
- 6.7 HVAC Secondary Systems
- 6.8 HVAC Primary Systems
- 6.9 Miscellaneous Energy Uses
- 6.10 On-Site Power Generation
- 6.11 Common Data Structures
- 6.11.1 Schedule
- 6.11.2 Holidays
- 6.11.3 Surface Geometry
- 6.11.4 Opening Geometry
- 6.11.5 Opening Shade
- 6.11.6 Construction Assembly
- 6.11.7 Fenestration Construction
- 6.11.8 Material
- 6.11.9 Slab Construction
- 6.11.10 Exterior Surface Properties
- 6.11.11 Building Shade
- 6.11.12 Utility Rate
- 6.11.13 Occupant Heat Rate
- 6.11.14 Furniture and Contents
- 6.11.15 Reference Position in a Space
- 6.11.16 Two Dimensional Curve
- 6.11.17 Three Dimensional Curve
- 6.11.18 Temperature Reset Schedule
- 6.11.19 Photovoltaic (PV) Panel
- 6.11.20 Contact
- 7 Advanced Modeling Tips
- 7.1 Challenging Building Types
- 7.2 Design Features
- 7.2.1 Automatically Controlled Window Shades
- 7.2.2 Active Chilled Beams
- 7.2.3 Dedicated Outside Air Systems (DOAS)
- 7.2.4 Displacement ventilation
- 7.2.5 Gas Engine Driven Heat Pumps
- 7.2.6 Ground Source Heat Pumps
- 7.2.7 Ice Storage Air Conditioners
- 7.2.8 Radiant Heating and/or Cooling
- 7.2.9 Switchable glazing
- 7.2.10 UFAD
- 7.2.11 Variable Refrigerant Flow
- Download Appendices