This group of building descriptors applies to proposed design systems that have reheat coils at the zone level. The building descriptors are applicable for baseline building systems 5 through 8.
Terminal Heat Type
|
| Applicability |
Systems that have reheat coils at the zone level |
| Definition |
The heating source for the terminal unit. This includes:
- Electric resistance
- Gas furnace
- Oil furnace
- Hot water
- Steam
|
| Units |
List (see above) |
| Input Restrictions |
As designed. |
| Baseline Rules |
Table 6.6.3-1 shows the terminal heat type for each baseline building system. |
Table 6.6.3-1: "Baseline Building Terminal Heat Type"
| Baseline building System |
Terminal Heat Type |
| System 1 – PTAC |
None |
| System 2 – PTHP |
None |
| System 3 – PSZ-AC |
None |
| System 4 – PSZ-HP |
None |
| System 5 – Packaged VAV with Reheat |
Hot Water |
| System 6 – Packaged VAV with PFP boxes |
Electric Resistance |
| System 7 – VAV with Reheat |
Hot Water |
| System 8 – VAV with PFP boxes |
Electric Resistance |
| Terminal Heat Capacity |
| Applicability |
Systems that have reheat coils at the zone level |
| Definition |
The heating capacity of the terminal heating source |
| Units |
Btu/h |
| Input Restrictions |
As designed. However, if the unmet load hours exceed 300, the energy analyst and design team may have to increase the size of the equipment so that the unmet load hours are less than 300. See Figure 6.1.2-1 and Figure 6.7.2-1. |
| Baseline Rules |
The software shall automatically size the terminal heating capacity to be 25% greater than the design loads. However, the equipment may need to be reduced in size such that the unmet load hours of the proposed design does not exceed the baseline building by more than 50. See Figure 6.7.2-1. |
Reheat Delta T
|
| Applicability |
Systems that have reheat coils at the zone level |
| Definition |
This is an alternate method to enter the terminal heat capacity. It can be calculated as follows:
(6.6.3-1)
where
Treheat
|
heat rise across the terminal unit heating coil (°F) |
| Treheat |
heating air temperature at design (°F) |
| Tcool_supply |
supply air temperature at the heating coil (°F) |
| Qcoil |
heating coil load (Btu/h) |
| CFM |
airflow (cfm) |
|
| Units |
Degrees Fahrenheit (°F) |
| Input Restrictions |
As designed, but may need to be increased if unmet load hours are greater than 300 |
| Baseline Rules |
Method not used for baseline building. See Heat Capacity above. |