6.7.4 Outdoor Air Controls and Economizers
Outside Air Controls
| Maximum Outside Air Ratio | |
| Applicability | All systems with modulating outside air dampers |
|---|---|
| Definition | The descriptor is used to limit the maximum amount of outside air that a system can provide as a percentage of the design supply air. It is used where the installation has a restricted intake capacity. |
| Units | Ratio |
| Input Restrictions | As designed |
| Baseline Rules | 1.0 |
| Design Outside Air Flow | |
| Applicability | All systems with outside air dampers |
|---|---|
| Definition | The rate of outside air that needs to be delivered by the system at design conditions. This input may be derived from the sum of the design outside air flow for each of the zones served by the system. |
| Units | cfm |
| Input Restrictions | As designed |
| Baseline Rules | Same as proposed design. This input along with occupant density determines if the zones served by the system shall have demand control ventilation. See ventilation control method at the zone level. |
| Outdoor Air Control Method | |
| Applicability | All HVAC systems that deliver outside air to zones |
|---|---|
| Definition | The method of determining the amount of outside air that needs to be delivered by the system. Each of the zones served by the system report their outside air requirements on an hourly basis. The options for determining the outside air at the zone level are discussed above. This control method addresses how the system responds to this information on an hourly basis. Options include:
The quantity of outside air can be controlled in a number of ways, but a common method is to install a flow station at the outside air supply which modulates the position of the outside air and return dampers to maintain the desired outside air flow. With the average flow, a CO2 sensor in the return air duct is another way to control the position of the outside air and return dampers. |
| Units | List (see above) |
| Input Restrictions | As designed |
| Baseline Rules | Same as proposed design |
Air Side Economizers
| Economizer Control Type | |
| Applicability | All systems with an air-side economizer |
|---|---|
| Definition | An air-side economizer increases outside air ventilation during periods when refrigeration loads can be reduced from increased outside air flow. The control types include:
|
| Units | List (see above) |
| Input Restrictions | As designed |
| Baseline Rules | The control should be no economizer when the baseline building cooling capacity 50 tons AND the baseline building system total cooling capacity 95,000 Btu/h. Otherwise, the control should be based on the prescribed system type as shown in Table 6.7.4-1. |
| Baseline building System | Economizer Control |
| System 1 – PTAC | None |
| System 2 – PTHP | None |
| System 3 – PSZ-AC | Differential dry-bulb None in climate zones 1a-4a and 1b |
| System 4 – PSZ-HP | Differential dry-bulb None in climate zones 1a-4a and 1b |
| System 5 – Packaged VAV with Reheat | Differential dry-bulb None in climate zones 1a-4a and 1b |
| System 6 – Packaged VAV with PFP boxes | Differential dry-bulb None in climate zones 1a-4a and 1b |
| System 7 – VAV with Reheat | Differential dry-bulb None in climate zones 1a-4a and 1b |
| System 8 – VAV with PFP boxes | Differential dry-bulb None in climate zones 1a-4a and 1b |
| Economizer High Temperature Lockout | |
| Applicability | Systems with fixed dry-bulb economizer |
|---|---|
| Definition | The outside air setpoint temperature above which the economizer will return to minimum position. |
| Units | Degrees Fahrenheit (°F) |
| Input Restrictions | As designed |
| Baseline Rules | Not applicable |
| Economizer Low Temperature Lockout | |
| Applicability | Systems with air-side economizers |
|---|---|
| Definition | A feature that permits the lockout of economizer operation (return to minimum outside air position) when the outside air temperature is below the lockout setpoint. |
| Units | Degrees Fahrenheit (°F) |
| Input Restrictions | As designed |
| Baseline Rules | Not used |
| Economizer High Enthalpy Lockout | |
| Applicability | Systems with fixed enthalpy or differential enthalpy economizers |
|---|---|
| Definition | The outside air enthalpy above which the economizer will return to minimum position |
| Units | Btu/lb |
| Input Restrictions | As designed. The default is 25 Btu/lb. |
| Baseline Rules | No lockout limit |
- PDF Version of Visible Section/s
- Generate Complete PDF
- Printer-friendly Version
- Login or register to post comments
Select a Purpose
Download PDF
Book Navigation
- Commercial Buildings Energy Modeling Guidelines & Procedures (MGP)
- Acknowledgments
- 1 Overview
- 2 General Modeling Procedures
- 3 Software Requirements
- 4 Content and Format of Standard Reports
- 5 Energy Costs and Currency Specification
- 6 Building Decriptors Reference
- 6.1 Overview
- 6.2 Project Data
- 6.3 Thermal Blocks
- 6.4 Space Uses
- 6.5 Building Envelope Data
- 6.6 HVAC Zone Level Systems
- 6.7 HVAC Secondary Systems
- 6.8 HVAC Primary Systems
- 6.9 Miscellaneous Energy Uses
- 6.10 On-Site Power Generation
- 6.11 Common Data Structures
- 6.11.1 Schedule
- 6.11.2 Holidays
- 6.11.3 Surface Geometry
- 6.11.4 Opening Geometry
- 6.11.5 Opening Shade
- 6.11.6 Construction Assembly
- 6.11.7 Fenestration Construction
- 6.11.8 Material
- 6.11.9 Slab Construction
- 6.11.10 Exterior Surface Properties
- 6.11.11 Building Shade
- 6.11.12 Utility Rate
- 6.11.13 Occupant Heat Rate
- 6.11.14 Furniture and Contents
- 6.11.15 Reference Position in a Space
- 6.11.16 Two Dimensional Curve
- 6.11.17 Three Dimensional Curve
- 6.11.18 Temperature Reset Schedule
- 6.11.19 Photovoltaic (PV) Panel
- 6.11.20 Contact
- 7 Advanced Modeling Tips
- 7.1 Challenging Building Types
- 7.2 Design Features
- 7.2.1 Automatically Controlled Window Shades
- 7.2.2 Active Chilled Beams
- 7.2.3 Dedicated Outside Air Systems (DOAS)
- 7.2.4 Displacement ventilation
- 7.2.5 Gas Engine Driven Heat Pumps
- 7.2.6 Ground Source Heat Pumps
- 7.2.7 Ice Storage Air Conditioners
- 7.2.8 Radiant Heating and/or Cooling
- 7.2.9 Switchable glazing
- 7.2.10 UFAD
- 7.2.11 Variable Refrigerant Flow
- Download Appendices

50 tons AND the baseline building system total cooling capacity