Baseline Building Summary. None of the baseline building systems use a water-side economizer.
| Water-Side Economizer Name |
| Applicability |
All water-side economizers |
| Definition |
The name of a water-side economizer for a cooling system
|
| Units |
Text, unique |
| Input Restrictions |
Descriptive reference to the construction documents. The default is no water-side economizer. |
| Baseline Rules |
No water economizer |
| Water Economizer Type |
| Applicability |
All water-side economizers |
| Definition |
The type of water-side economizer. Choices include:
- None
- Heat exchanger in parallel with chillers. This would be used with an open cooling tower is often referred to as a non-integrated economizer, because the chillers are locked out when the plant is in economizer mode.
- Heat exchanger in series with chillers. This would be used with an open cooling tower and is often referred to as an integrated, because the chillers can operate simultaneously with water economizer operation.
- Direct water economizer. This would be used with a closed cooling tower. In this case, a heat exchanger is not needed. This type works only as a non-integrated economizer.
- Thermo-cycle (also known as refrigerant migration). With thermo-cycle, bypass valves allow for the flow to vapor refrigerant to the condenser and allow gravity flow of liquid refrigerant to the evaporator without use of the compressor. Only some chillers have this capability and capacity may be limited under this mode. There is no additional piping; the cooler water from the tower is brought directly to the chiller(s) and the chiller(s) respond by shutting down the compressor and relying on thermal forces to drive the refrigerant. This method is also known as “thermosiphon” since thermal gradients passively move refrigerant between the evaporator and condenser.
|
| Units |
List (see above) |
| Input Restrictions |
As designed |
| Baseline Rules |
No water economizer |
| Water-Side Economizer HX Effectiveness |
| Applicability |
Water-side economizers with an open cooling tower |
|
Definition
|
The effectiveness of a water-side heat exchanger at design conditions. This is defined as:
(6.8.4-1)
where
| WSEeff |
The effectiveness of the water-side economizer coil |
| tea |
The entering coil air dry-bulb temperature (°F) |
| tla |
The leaving coil air dry-bulb temperature (°F) |
| tea |
The entering coil water temperature (°F) |
|
| Units |
Ratio |
| Input Restrictions |
As designed. The default is 60 %. |
| Baseline Rules |
No water economizer |
| Water-Side Economizer Maximum Tdb |
| Applicability |
All water-side economizers |
| Definition |
The control temperature (outside air dry-bulb temperature) above which the water-side economizer is disabled. |
| Units |
Degrees Fahrenheit (°F)
|
| Input Restrictions |
As designed. Defaults to 65°F. |
| Baseline Rules |
No water economizer |
Water-Side Economizer Maximum CWS
|
| Applicability |
All water-side economizers |
| Definition |
The control temperature (condenser water supply temperature) above which the water-side economizer is disabled. |
| Units |
Degrees Fahrenheit (°F) |
| Input Restrictions |
As designed. Defaults to 50°F. |
| Baseline Rules |
No water economizer
|
| Water-Side Economizer CWS Setpoint |
| Applicability |
All water-side economizers |
| Definition |
The design condenser water supply temperature for the cooling tower in economizer mode.
|
| Units |
Degrees Fahrenheit (°F)
|
| Input Restrictions |
As designed. Defaults to 45°F or 40°F for “Thermo Cycle.” |
| Baseline Rules |
No water economizer |
Water-Side Economizer Availability Schedule
|
| Applicability |
All water-side economizers
|
| Definition |
A schedule which represents the availability of the water-side economizer |
| Units |
Data structure: schedule, on/off |
| Input Restrictions |
As designed
|
| Baseline Rules |
No water economizer |
Water-Side Economizer Auxiliary kW
|
| Applicability |
Water-side economizers with an open tower |
| Definition |
The electrical input (pumps and auxiliaries) for a dedicated pump for the chilled water side of the heat exchanger. This power is in excess of the condenser water pumps and cooling tower fans for the system during water-side economizer operation.
|
| Units |
KW or kW/ton |
| Input Restrictions |
As designed |
| Baseline Rules |
No water economizer |